HRL1280W csb battery 12V Suitable for UPS backup for large data centers, HVDC backup for cloud computing centers, Uninterruptible power supply for financial trading systems
For data center UPS and other applications requiring high-rate float standby power, the CSB HRL1280W belongs to the HRL series and is a 12V valve-regulated sealed lead-acid battery; its construction combines AGM technology and pure lead, with a 15-minute rate nominal capacity of 80W.
Taobao store
WeChat procurement
Product Features
- Type: VRLA valve-regulated lead-acid battery
- Maintenance-free design; uses AGM (Absorbent Glass Mat) technology, with gas recombination efficiency up to 99%
- Construction material is pure lead, with proprietary elements added
- Applications: high-rate UPS, float-charge standby power
- Standards and certifications: manufactured to IEC 61056-1/2:2012; UL1989 Recognized (MH14533)
Application Scenarios
- UPS backup for large data centers
- HVDC backup for cloud computing centers
- Uninterruptible power supply for financial trading systems
- UPS emergency protection for communications hubs
- High-power UPS backup for industrial automation
- UPS backup for rail transit signaling
Product parameters
- Model:HRL1280W
- Voltage:12 Vdc
- Nominal Capacity:80W @15min-rate
- Watts per Cell:161.83 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:80.83 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:8.0 A
- Max. Discharge Current:300 A
- Short Circuit Current:723 A
- Internal Resistance:9.00 mΩ
- Terminal Type:I1 thread lead alloy terminal to accept M5 bolt
- Terminal Torque:30.4±6.1 Kgf·cm / 26.4±5.3 Lbf·in / 3.0±0.6 N·m
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:6.60 / 14.55 kg / lb.
- Length (L):181.0±2.0 / 7.13±0.08 mm / in
- Width (W):76.0±1.0 / 2.99±0.04 mm / in
- Height (H):165.0±2.0 / 6.50±0.08 mm / in
- Design Life:Up to 8 years in standby service at 25°C; Eurobat (20°C): 10-12 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
HRL1280W has a voltage of 12 Vdc. At 1.67 VPC and 25°C, its 15-minute rate nominal capacity is 80W; the 5-minute rate power reaches 161.83 W/cell, while the 15-minute rate power is 80.83 W/cell. The maximum charging current is 8.0 A, the maximum discharging current is 300 A, short-circuit current is 723 A, and internal resistance is 9.00 mΩ. Float charging voltage range is 13.5 to 13.8 Vdc/battery (25°C), and equalization charging voltage range is 14.4 to 15.0 Vdc/battery (25°C).
HRL1280W belongs to the HRL series. Its product category is 6V and 12V top terminal valve-regulated sealed lead-acid batteries. It uses a valve-regulated sealed structure and absorbent glass mat (AGM) technology, with gas recombination efficiency up to 99%, achieving maintenance-free operation. This series focuses on long life and high rate, and is a pure lead UPS battery designed for data centers and UPS loads with demanding power requirements; its official application field is data center uninterruptible power supplies.
Length, width, and height are 181.0±2.0 mm, 76.0±1.0 mm, and 165.0±2.0 mm respectively, with a weight of 6.60 kg. The I1 threaded lead alloy terminal is compatible with M5 bolts, with torque of 30.4±6.1 Kgf·cm, 26.4±5.3 Lbf·in, or 3.0±0.6 N·m. The case uses ABS (UL 94-HB); a flame-retardant 94-V0 version is available on request.
Nominal temperature is 25°C; discharge is allowed from -15°C to 50°C; charging and storage are allowed from -15°C to 40°C. Self-discharge is less than 10% after 90 days at 25°C. Storage at 25°C is up to 6 months, and the battery should be fully charged before use; if storage temperature exceeds 25°C, recharge earlier. Under 25°C float charging conditions, design life is up to 8 years; Eurobat (20°C) is 10 to 12 years standard commercial. Manufacturing standard is IEC 61056-1/2:2012, and it is UL1989 recognized (MH14533).